Cable Voltage Drop Calculator

Voltage drop is the voltage lost along a cable's conductors under load current — ΔU = 2 × I × R × L / 1000 for a single-phase two-wire circuit and ΔU = √3 × I × (R × cos φ + X × sin φ) × L / 1000 for a three-phase circuit. This calculator applies the maximum DC resistances of IEC 60228 with 20/70/90 °C temperature correction, checks the result against a 3–10 % limit, and — in reverse mode — returns the maximum route length your limit allows.

Calculator

Calculate Voltage Drop or Maximum Length

Results update as you type. Conductor resistance is taken from the embedded IEC 60228 table for standard sections; non-standard sections are estimated from nominal resistivity and flagged.

Solve for

Reverse mode: given the load and your drop limit, how long can the run be?

System

Balanced three-phase load assumed (no neutral current).

Presets 230 / 400 / 690 / 1000 V — edit freely. Three-phase: line-to-line voltage.

Load input

kW mode converts to current with cos φ: I = P×1000 / (U·cos φ), or ÷√3 for three-phase.

Steady-state load current, not cable rating.

Single run of the circuit — the single-phase formula counts the return conductor automatically.

Used in the three-phase R·cos φ + X·sin φ term and in kW→A conversion.

Conductor material

IEC 60228 lists aluminium resistances from 16 mm² up; smaller sections are estimated from ρ.

Standard IEC sections use the IEC 60228 maximum resistance; any other value is estimated from ρ.

Conductor working temperature

Resistance corrected from 20 °C by αCu = 0.00393/K, αAl = 0.00403/K.

European installation practice commonly applies 5 % from supply to load (3 % for lighting).

Advanced — conductor reactance X (Ω/km)

Default 0.08 Ω/km is typical for LV multicore cable. Used in the X·sin φ term of the three-phase formula; the single-phase formula shown here neglects reactance.

Formula

The Voltage Drop Formula — and What It Assumes

ΔU = 2 × I × R × L / 1000 single-phase two-wire circuit (out and back conductors)

ΔU = √3 × I × (R × cos φ + X × sin φ) × L / 1000 three-phase three-wire circuit, balanced load

ΔU% = ΔU / U × 100 voltage drop as a percentage of the rated voltage

RT = R20 × (1 + α × (T − 20)) resistance at conductor working temperature T; αCu = 0.00393/K, αAl = 0.00403/K

Lmax = 1000 × ΔUmax / (2 × I × R) reverse mode: longest one-way route that meets the limit, ΔUmax = U × limit / 100; three-phase divides by √3 × I × (R·cos φ + X·sin φ) instead

Stated assumptions

  • R is the conductor resistance at the working temperature, built from the maximum DC resistance values of IEC 60228 at 20 °C (the same values behind GB/T 3956 and EN 60228) with the linear temperature correction above. Sections not listed in IEC 60228 are estimated from nominal resistivity (ρCu = 0.0175, ρAl = 0.0278 Ω·mm²/m) and flagged as estimates.
  • L is the one-way route length; the factor 2 in the single-phase formula counts the return conductor.
  • The single-phase formula uses the resistance term only — series reactance is neglected, a sound simplification for small-section two-wire circuits.
  • The three-phase formula includes the reactance term X × sin φ (default X = 0.08 Ω/km for LV multicore cable). With X = 0 or cos φ = 1 it reduces to the resistance term.
  • A balanced three-phase load is assumed (no neutral current), and the result is the steady-state drop at the entered load — not motor-starting peaks.

Reference Data

Conductor DC Resistance per IEC 60228

Maximum conductor resistance at 20 °C in Ω/km for single-wire and stranded (class 1 and 2) conductors. Resistance values per IEC 60228 — the standard behind EN 60228 and GB/T 3956, and the basis of this calculator.

Max. DC resistance at 20 °C (Ω/km) — IEC 60228, classes 1–2
Nominal section (mm²)Copper Cu (Ω/km)Aluminium Al (Ω/km)
1.512.1—
2.57.41—
44.61—
63.08—
101.83—
161.151.91
250.7271.20
350.5240.868
500.3870.641
700.2680.443
950.1930.320
1200.1530.253
1500.1240.206
1850.09910.164
2400.07540.125
3000.06010.100
4000.04700.0778
5000.03660.0605
6300.02830.0469

IEC 60228 standardises aluminium conductors from 16 mm² upward — smaller aluminium sections (shown as “—”) are outside the standard and rare in European practice. The values are maximum resistances: a real conductor may measure slightly lower, so drops calculated from them are slightly conservative. For flexible (class 5) copper conductors the maxima are a few percent higher; for exact class-5 verification send us the schedule.

Applications

Where Voltage Drop Decides the Cable

LV Power

LV power & utility feeds

On 230/400 V distribution the 5 % limit quickly sizes the conductor: a 100 m feeder at 100 A needs 35 mm² Cu or larger to stay inside it. Grid and substation works use the same check at 690/1000 V.

Portable and tool feeds on rubber cable follow the same physics — see the rubber & flexible families (H07RN-F & H05RN-F) and the voltage class ladder for which rated voltage applies to which family. Comparing copper against an aluminium alternative for the same run? Use our copper/aluminium section converter.

FAQ

Cable Voltage Drop — Quick Answers

European installation practice — following IEC 60364-5-52 and national wiring rules such as BS 7671 — commonly limits voltage drop to 3 % for lighting circuits and 5 % for other uses, measured from the origin of the installation to the load. The calculator defaults to 5 % and offers 3, 4, 5 and 10 % (10 % is used for dedicated motor feeds and long rural runs).
Single-phase two-wire: ΔU = 2 × I × R × L / 1000. Three-phase three-wire: ΔU = √3 × I × (R × cos φ + X × sin φ) × L / 1000. R is the conductor resistance at working temperature taken from IEC 60228 maximum values at 20 °C, corrected with αCu = 0.00393/K or αAl = 0.00403/K; L is the one-way route length in metres; X is the conductor reactance (default 0.08 Ω/km, three-phase only).
Switch the load input to Power (kW). The calculator converts P to current with I = P × 1000 / (U × cos φ) for single-phase and I = P × 1000 / (√3 × U × cos φ) for three-phase, then applies the voltage drop formula. Example: 15 kW at 400 V three-phase, cos φ 0.85 gives I = 25.47 A.
Metal resistance rises with temperature: RT = R20 × (1 + α × (T − 20)), with α about 0.00393/K for copper and 0.00403/K for aluminium. A 90 °C XLPE conductor therefore carries about 27.5 % more resistance than its 20 °C IEC value — a warm cable drops more voltage than a cold one, which is why the calculator defaults to 90 °C.
Yes, on three-phase circuits. The drop vector splits into a resistance component in phase with the current (R × cos φ) and a reactance component (X × sin φ). At cos φ = 1 the X term vanishes; at lower power factors on large sections the reactance term can dominate, because X barely changes with section while R falls rapidly. The single-phase formula shown here neglects reactance, which is reasonable for small two-wire circuits.
Switch the calculator to Max. route length: enter the load, conductor and limit, and it inverts the formula — Lmax = 1000 × ΔUmax / (2 × I × R) for single-phase (three-phase: divide by √3 × I × (R·cos φ + X·sin φ) instead), where ΔUmax = U × limit / 100. Example: 25 A at 230 V single-phase, 4 mm² copper, 5 % limit → 49.9 m.

Long Run? Send It In

We check voltage drop on every quotation.

Send the route length, load and system voltage with your enquiry — our engineers verify the drop, the current rating and the insulation class against your installation rules, and propose the section that passes on the first submission.

Request a Custom Quote Cu / Al Converter