EN

Custom Case — Sweden

From National Designations to Equivalents: Custom SS Cable for the Swedish Grid

A de-identified case from a Swedish grid operator, in summary: a cable requirement written in national SS designations, from low-voltage mains to medium-voltage direct-burial cable, answered with equivalents. This page covers the products involved and what we customize — project specifics stay confidential.

Swedish grid utilities write their cable requirements in national SS designations — N1XE, AXLJ-F, AXAL-TT — rather than harmonised EN 50525 or IEC types, and none of those designations belong to the harmonised international catalogs. Every letter has to be decoded into construction data first; that is where a standard catalog ends and custom-by-standard work begins. This case summarises one such requirement — de-identified to the customer, its country and its working condition — and the products it asked of us.

The Swedish SS cable designation families: N1XE low-voltage mains, ALUS aerial bundled, AXLJ-F single-core 12 kV, and AXC LIGHT-TT and AXAL-TT three-core medium-voltage direct-burial cable

The customized products

The Swedish grid-cable families are all constructions we build and customize to the Swedish SS standards — copper and aluminium conductors, XLPE insulation, PE and HDPE sheaths, metallic screens, water-tightness where the grid buries its cable. The table shows the families behind this case, and the figure above shows how they cover the grid’s voltage span.

The SS-standard cable families behind this case — each a construction we build and customize
FamilyVoltageConstructionDuty
N1XE0.6/1 kVCu & Al · XLPE · PE sheath · solid, stranded or sector conductorsLV distribution mains
SE-N1XE0.6/1 kVfive-core type in the CENELEC-style codeLV mains with an additional core
ALUS0.6/1 kVAl · PE insulation · self-supporting bundledaerial pole-line service
AXLJ-F12 kVAl single-core · XLPE · PE sheath · screen by cross-sectiontransformer stations, switchyards
AXC LIGHT-TT12 kVthree-core Al · XLPE · HDPE · copper-wire screen · water-tightdirect-burial / plough-in MV
AXAL-TT24 kVthree-core Al · XLPE · HDPE · aluminium-wire screen · water-tightMV direct burial

The LV mains follow SS 424 14 18, the three-core MV types SS 424 14 16 and the aerial family SS 424 14 26 — each construction validated field by field in the 48-hour technical review. And every equivalent carries the buyer’s designation in its sheath marking, because the crews who install it read Swedish grid designations, not IEC ones.

How the designations read

Swedish cable designations follow two published letter systems, and a grid requirement typically carries both. The modern SS 424 17 02 code (CENELEC style) writes the low-voltage mains families: N is a national type built to the Swedish SS series, 1 is 0.6/1 kV, X is XLPE insulation, E is a PE outer sheath. Conductor suffixes come from EN 60228: -U is a solid round conductor (class 1), -R a stranded round conductor (class 2), -AS an aluminium conductor of stranded, sector-shaped cross-section. The SE- prefix is simply Sweden’s two-letter country code in the CENELEC designation system — the same cable family, written the international way.

The classic SS 424 17 01 code, still used for the MV families, reads from the inside out: A is an aluminium conductor, X is XLPE insulation, L is a PE — on the three-core types, HDPE — sheath, J marks a construction rated for direct burial. Where a screen letter appears, C is a concentric copper-wire screen and A an aluminium-wire screen — the AXAL-TT family; the AXLJ-F articles specify their screen by cross-section instead. The suffix TT (totaltät) means totally water-tight in both directions: radially, through an aluminium laminate bonded to the sheath, and longitudinally, through swelling elements — the construction Swedish grid practice demands of plough-in and direct-buried medium-voltage cable.

How Swedish designations decode: the modern SS 424 17 02 letters N, 1, X, E with conductor suffixes -U, -R, -AS and the SE country prefix, and the classic SS 424 17 01 letters A, X, L, J with TT total water-tightness and screen sections in square millimetres

Some suffixes belong to the buyer’s own catalog rather than the national letter tables; they are read against the buyer’s specification and mapped case by case. That is what the 48-hour technical review is for: by the end of it, every designation is a validated construction sheet, not a string of letters.

How such an answer runs

An equivalent runs through the same five-step flow as any custom order. The 48-hour technical review decodes each designation into a validated construction sheet — conductor, insulation, sheath, screen, water-tightness, voltage class. Samples of the equivalent construction are produced and tested within 7–15 days of the review, rush slots typically 5. Small-batch production runs about 25 days, rush around 15, and every production batch leaves with routine test reports — conductor resistance, high-voltage withstand, insulation resistance — alongside the CoC. Equivalents of national types are custom-by-standard productions, quoted by production run, with the quantity confirmed at quotation — the same low-MOQ entry as any TongYuan order.

Where national designations sit in our work

This case is one instance of the service described in Custom by Standard: BS, VDE, NF, UNE, EN 50525, IEC, GB — and the Swedish SS families — are one discipline: read the designation, validate the construction, sample it, produce it, document it. The five-step flow such an answer runs through is described in From Drawing to Delivery; the buyer-side checks that make such an answer verifiable are collected in the buying checklist; and the low-voltage sections of a grid bill of materials can be re-checked against route length with the voltage-drop calculator before the order is confirmed. If your market’s requirement is written in a national designation we have never built, the RFQ desk is the entry point: the specification alone is enough to start, the 48-hour review decodes it, and the first response comes within 3 working hours.

FAQ

Swedish SS Cable — Quick Answers

Yes — SS national families are part of our custom-by-standard work: 0.6/1 kV mains to SS 424 14 18, three-core MV to SS 424 14 16, aerial bundled to SS 424 14 26. The construction is validated field by field in the 48-hour technical review and sampled before any volume.
The buyer’s designation is their catalog standard. An equivalent must match its construction field by field — conductor class, insulation, sheath, screen and water-tightness — and carry the same designation in the sheath marking. Our mapping sheet sets the required designation, the decoded construction and our article number side by side.
0.6/1 kV mains in the N1XE family, 0.6/1 kV aerial bundled in the ALUS family, 12 kV single-core station cable in the AXLJ-F family, and 12/24 kV three-core direct-burial cable in the AXC LIGHT-TT and AXAL-TT families — the span a Swedish grid bill of materials typically covers.
Samples of the equivalent construction are produced and tested within 7–15 days of the technical review, rush slots typically 5 days. Small-batch production runs about 25 days, rush around 15, and every batch leaves with routine test reports — conductor resistance, high-voltage withstand, insulation resistance — alongside the CoC.
Letter by letter: N is a national type built to the Swedish SS series, 1 is 0.6/1 kV, X is XLPE insulation, E is a PE outer sheath, and -U is a solid round conductor (class 1) — the designation itself carries the construction. The classic MV code reads the same way: A is aluminium, X is XLPE, L is a PE sheath, J is direct burial, and TT marks total water-tightness.

National Standards, Decoded

Send the requirement — even if it is written in a national code we have never built.

The 48-hour review decodes the designation into a validated construction; samples are produced and tested in 7–15 days; custom runs are quoted by production run. Custom by Standard is where this service is described; the RFQ desk is where it starts.

Send Your Requirement How Custom by Standard Works