An equal-resistance aluminium conductor needs SAl = SCu × (ρAl/ρCu) ≈ 1.59 × SCu of cross-section, because aluminium’s volume resistivity at 20 °C (≈ 0.0278 Ω·mm²/m) is about 1.59 times copper’s (≈ 0.0175 Ω·mm²/m). This converter works the rule in both directions, pairs the sections with unit weights (Cu 8.89 / Al 2.70 g/cm³) and 20 °C resistances, and rounds up to the next standard IEC 60228 size — current capacity must be verified separately.

Converter

Convert a Section Both Ways

Results update as you type. The equivalent section keeps the resistance identical; the “next standard size” is the smallest IEC 60228 section that is still at or above it.

Conversion direction

Equal-resistance conversion: SAl = SCu × 1.59, or SCu = SAl ÷ 1.59.

Any value works; standard IEC sections are offered as suggestions.

Formula

The Equal-Resistance Rule — and What It Assumes

SAl = SCu × (ρAl / ρCu) ≈ SCu × 1.59 equal-resistance section conversion, 20 °C nominal resistivities

SCu = SAl ÷ (ρAl / ρCu) ≈ SAl ÷ 1.59 reverse direction of the same rule

R = ρ × 1000 / S conductor resistance in Ω/km from resistivity ρ (Ω·mm²/m) and section S (mm²)

W = S × d unit weight in kg/km from section S (mm²) and density d (g/cm³): Cu 8.89, Al 2.70

Stated assumptions

  • The conversion is equal-resistance: both conductors have the same DC resistance per kilometre at 20 °C. It is the criterion used when substituting material on a voltage-drop-limited circuit.
  • Nominal volume resistivities are used: ρCu = 0.0175 and ρAl = 0.0278 Ω·mm²/m at 20 °C (ratio 1.5886 ≈ 1.59). Standardised IEC 60228 maximum resistances run a few percent higher and are listed for reference in the tables below.
  • The “next standard size” rounds the exact equivalent up to the smallest IEC 60228 section at or above it, so the substituted conductor is never undersized in resistance. Aluminium starts at 16 mm² in IEC 60228.
  • Weights are bare-conductor values from the densities Cu 8.89 and Al 2.70 g/cm³; insulation, screens and armour add to both.
  • Current capacity is not converted. Ampacity depends on construction, installation and standard — an equal-resistance aluminium cable is typically about one IEC size larger in rating terms as well, but it must be verified against the relevant standard and the accessories must be aluminium-rated.

Reference Data

Copper to Aluminium Quick Reference

Exact equal-resistance equivalents with the next standard IEC 60228 section, unit weights and the 20 °C resistances behind them. Resistance values per IEC 60228.

Cu → Al equal-resistance substitution (nominal ρ ratio 1.59; weights from densities 8.89 / 2.70 g/cm³)
Cu section (mm²)Exact Al equivalent (mm²)Next standard Al (mm²)Cu weight (kg/km)Al weight (kg/km)Cu R20 IEC max (Ω/km)Al R20 IEC max (Ω/km)
1625.435142.268.61.150.868
2539.750222.3107.20.7270.641
3555.670311.2150.10.5240.443
5079.495444.5214.50.3870.320
70111.2120622.3300.20.2680.253
95150.9185844.6407.50.1930.164
120190.62401066.8514.70.1530.125
150238.32401333.5643.40.1240.125
185293.93001644.7793.50.09910.100
240381.34002133.61029.40.07540.0778
300476.65002667.01286.70.06010.0605
400635.4beyond 630 — custom3556.01715.70.04700.0469

Reading the table: a 50 mm² copper conductor is matched in resistance by 79.4 mm² of aluminium — the smallest standard section at or above that is 95 mm², whose IEC 60228 maximum (0.320 Ω/km) sits well below copper’s 0.387 Ω/km — while the conductor weight drops from 444.5 to 214.5 kg/km. In the mid range the chosen aluminium size clears the copper’s IEC maximum resistance outright (95 mm² Cu → 185 mm² Al: 0.164 vs 0.193 Ω/km). At 150–300 mm² the two maxima fall within about one percent of each other because tolerance bands differ by size, so the substitution guarantee rests on the nominal equal-resistance rule with margins taken from the current-rating and voltage-drop verification. And at 400 mm² the exact equivalent (635.4 mm²) tops the largest IEC 60228 size — custom-build territory, though 630 mm² aluminium still edges the copper maximum (0.0469 vs 0.0470 Ω/km).

Reference Data

AWG / kcmil to mm² Cross-Reference

US sizes on a drawing or an enquiry? Metric sections from ASTM B258 areas, with the nearest IEC 60228 standard section for specification work.

AWG and kcmil cross-sections to metric areas (ASTM B258) with nearest IEC standard size
Size (AWG / kcmil)Area (mm²)Nearest IEC 60228 section (mm²)
18 AWG0.8231.5
16 AWG1.311.5
14 AWG2.082.5
12 AWG3.314
10 AWG5.266
8 AWG8.3710
6 AWG13.316
4 AWG21.225
2 AWG33.635
1 AWG42.450
1/0 AWG53.550
2/0 AWG67.470
3/0 AWG85.095
4/0 AWG107.295
250 kcmil126.7120
350 kcmil177.3185
500 kcmil253.3240
750 kcmil380.0400
1000 kcmil506.7500

“Nearest” is by absolute area — when converting a US size into a metric build for a European installation, round up to the next standard section instead, exactly as the converter does for Cu–Al substitutions. 4/0 AWG (107.2 mm²) illustrates the difference: the nearest IEC size is 95 mm², but the next size up is 120 mm².

Engineering Sense

What Switching Copper to Aluminium Really Buys

Cost

Conductor cost

The aluminium substitute needs about 1.59 × the metal volume, but aluminium trades at a fraction of copper’s price per kilogram — so an equal-resistance aluminium conductor is almost always the cheaper option, and the gap widens whenever copper spikes.

Weight

Weight — roughly half

With aluminium at 2.70 g/cm³ against copper’s 8.89 g/cm³, the equal-resistance aluminium conductor weighs about 48 % of the copper one — 214 kg/km against 445 kg/km at 50 mm² Cu. Lighter drum handling and lower supported-load structures follow.

Caveats

What it does not convert

Ampacity, short-circuit rating, flexibility and terminations are not covered by the resistance rule. Aluminium needs larger sections (IEC 60228 lists it from 16 mm²), Al-rated or bimetallic lugs, anti-oxide joint preparation, and more care on flexing duty — reeling and mining cables therefore stay copper.

In practice the substitution pays off on fixed LV distribution — utility feeds and aerial bundled conductor in the utilities & power grid sector — where routes are long, loads are static and the voltage-drop check (run our voltage drop calculator with the converted section) does the sizing. Shipboard installations to IEC 60092 mostly remain copper for robustness and terminations, while the voltage class of the cable is unchanged by a material swap. If your schedule specifies a copper section and you are weighing the aluminium alternative, our engineers price both under the Custom by Standard route.

FAQ

Copper vs Aluminium Cable — Quick Answers

About 1.59 times: SAl = SCu × (ρAl/ρCu) with ρAl ≈ 0.0278 and ρCu ≈ 0.0175 Ω·mm²/m at 20 °C, so 50 mm² of copper corresponds to 79.4 mm² of aluminium — choose the standard 95 mm². For the same current rating rather than the same resistance, verify the ampacity tables separately.
Yes — roughly half. The aluminium section is 1.59 × larger, but aluminium weighs 2.70 g/cm³ against copper’s 8.89 g/cm³, so the equal-resistance aluminium conductor weighs about 48 % of the copper one: 214 kg/km against 445 kg/km at 50 mm² Cu → 79.4 mm² Al. The overall cable is heavier than its bare conductor, so realised savings on the finished cable are smaller.
Because small aluminium conductors are neither economic nor robust: at small sections the mechanical weakness of aluminium, its larger diameter and the connection requirements outweigh the material saving, so European standardisation starts aluminium at 16 mm² (IEC 60228, identical in EN 60228 and GB/T 3956). Below that, copper is the practical conductor.
No. A same-section aluminium conductor has about 1.59 × the resistance and a lower current rating, so voltage drop and ampacity both degrade. Convert the section with the rule above (or this tool), re-check the current rating for the aluminium construction, and use aluminium-rated or bimetallic terminations with anti-oxide preparation — copper lugs on aluminium conductors are a classic failure point.
Aluminium and copper constructions are both quotable across the LV power families — send the schedule through the RFQ desk with your preferred material and route, and we quote both variants where the standard allows. Mining, reeling and shipboard families per IEC 60092 remain copper by standard practice, as explained in our mining cable and shipboard cable guides.

Both Variants, One Drawing

Send the schedule — we quote Cu and Al side by side.

Give us the route, the load and your standard (IEC, EN, BS, VDE, NF or GB): our engineers return the copper build, the aluminium alternative with the verified section, and the voltage-drop check that proves both pass.

Request a Custom Quote Voltage Drop Calculator