LV power & utility feeds
On 230/400 V distribution the 5 % limit quickly sizes the conductor: a 100 m feeder at 100 A needs 35 mm² Cu or larger to stay inside it. Grid and substation works use the same check at 690/1000 V.
Engineering Tools
Voltage drop is the voltage lost along a cable's conductors under load current — ΔU = 2 × I × R × L / 1000 for a single-phase two-wire circuit and ΔU = √3 × I × (R × cos φ + X × sin φ) × L / 1000 for a three-phase circuit. This calculator applies the maximum DC resistances of IEC 60228 with 20/70/90 °C temperature correction, checks the result against a 3–10 % limit, and — in reverse mode — returns the maximum route length your limit allows.
Calculator
Results update as you type. Conductor resistance is taken from the embedded IEC 60228 table for standard sections; non-standard sections are estimated from nominal resistivity and flagged.
Formula
ΔU = 2 × I × R × L / 1000 single-phase two-wire circuit (out and back conductors)
ΔU = √3 × I × (R × cos φ + X × sin φ) × L / 1000 three-phase three-wire circuit, balanced load
ΔU% = ΔU / U × 100 voltage drop as a percentage of the rated voltage
RT = R20 × (1 + α × (T − 20)) resistance at conductor working temperature T; αCu = 0.00393/K, αAl = 0.00403/K
Lmax = 1000 × ΔUmax / (2 × I × R) reverse mode: longest one-way route that meets the limit, ΔUmax = U × limit / 100; three-phase divides by √3 × I × (R·cos φ + X·sin φ) instead
Reference Data
Maximum conductor resistance at 20 °C in Ω/km for single-wire and stranded (class 1 and 2) conductors. Resistance values per IEC 60228 — the standard behind EN 60228 and GB/T 3956, and the basis of this calculator.
| Nominal section (mm²) | Copper Cu (Ω/km) | Aluminium Al (Ω/km) |
|---|---|---|
| 1.5 | 12.1 | — |
| 2.5 | 7.41 | — |
| 4 | 4.61 | — |
| 6 | 3.08 | — |
| 10 | 1.83 | — |
| 16 | 1.15 | 1.91 |
| 25 | 0.727 | 1.20 |
| 35 | 0.524 | 0.868 |
| 50 | 0.387 | 0.641 |
| 70 | 0.268 | 0.443 |
| 95 | 0.193 | 0.320 |
| 120 | 0.153 | 0.253 |
| 150 | 0.124 | 0.206 |
| 185 | 0.0991 | 0.164 |
| 240 | 0.0754 | 0.125 |
| 300 | 0.0601 | 0.100 |
| 400 | 0.0470 | 0.0778 |
| 500 | 0.0366 | 0.0605 |
| 630 | 0.0283 | 0.0469 |
IEC 60228 standardises aluminium conductors from 16 mm² upward — smaller aluminium sections (shown as “—”) are outside the standard and rare in European practice. The values are maximum resistances: a real conductor may measure slightly lower, so drops calculated from them are slightly conservative. For flexible (class 5) copper conductors the maxima are a few percent higher; for exact class-5 verification send us the schedule.
Applications
On 230/400 V distribution the 5 % limit quickly sizes the conductor: a 100 m feeder at 100 A needs 35 mm² Cu or larger to stay inside it. Grid and substation works use the same check at 690/1000 V.
Face machinery sits hundreds of metres from the substation, and excavator trailing cables grow longer as the cut advances — drop at the machine terminals hits starting torque. The voltage classes behind these runs are explained in Decoding Chinese Mining Cable Designations.
Ship runs are long and steel hulls restrict conductor sizes: bow thrusters and winches on 0.6/1 kV IEC 60092 feeds are classic drop-sensitive loads. The cable families are decoded in Reading Shipboard Cable Codes.
Portable and tool feeds on rubber cable follow the same physics — see the rubber & flexible families (H07RN-F & H05RN-F) and the voltage class ladder for which rated voltage applies to which family. Comparing copper against an aluminium alternative for the same run? Use our copper/aluminium section converter.